Blue Commercial Thermostat with
Automatic Heat/Cool Changeover
Option and Damper Control
Model Programming Choices
1F95-0680
7 Day 5/1/1 Day Non-Programmable
Single Stage, Multi-Stage, Heat Pump
Installation and Operating Instructions for Model:
APPLICATIONS
THERMOSTAT APPLICATION GUIDE
1F95-0680 Commercial Thermostat
SPECIFICATIONS
To prevent electrical shock and/or equipment damage,
disconnect electric power to system at main fuse or
circuit breaker box until installation is complete.
CAUTION
!
Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS
CAREFULLY BEFORE INSTALLING OR OPERATING THIS
CONTROL COULD CAUSE PERSONAL INJURY AND/OR
PROPERTY DAMAGE.
Description
Heat Pump (No Aux. or Emergency Heat)
Ye s
Heat Pump (with Aux. or Emergency Heat)
Ye s
Systems with up to 4 Stages Heat, 2 Stages Cool
Ye s
Heat Only Systems
Ye s
Millivolt Heat Only Systems – Floor or Wall Furnaces
Ye s
Cool Only Systems
Ye s
Gas or Oil Heat
Ye s
Electric Furnace
Ye s
Hydronic (Hot Water) Zone Heat – 2 Wires
Ye s
Hydronic (Hot Water) Zone Heat – 3 Wires
Ye s
Wired Remote Temperature Sensor (Indoor or Outdoor)
Ye s
Dual Fuel Feature (Heat Pump Mode, Outdoor Remote
Required) or Damper Control Feature
Ye s
ATTENTION: MERCURY NOTICE
This product does not contain mercury. However, this prod-
uct may replace a product that contains mercury.
Mercury and products containing mercury must not be
discarded in household trash. Do not touch any spilled
mercury. Wearing non-absorbent gloves, clean up any
spilled mercury and place in a sealed container. For proper
disposal of a product containing mercury or a sealed
container of spilled mercury, place it in a suitable shipping
container. Refer to www.thermostat-recycle.org for loca-
tion to send product containing mercury.
Index Page
Installation 2
Wiring Diagrams 3
Thermostat Quick Reference 5
Installer Configuration Menu 6
Operating Your Thermostat 9
Programming 10
Troubleshooting 14
Electrical Rating:
Battery Power .......................... mV to 30 VAC, NEC Class II, 50/60 Hz or DC
Input-Hardwire ......................... 20 to 30 VAC
Terminal Load ............................. 1.5A per terminal, 2.5A maximum all terminals combined
Setpoint Range ............................ 45 to 99°F (7 to 32°C)
Differential (Single Stage) .................... Heat 0.6°F; Cool 1.2°F
Differential (Multi-Stage) ..................... Heat 0.6°F; Cool 1.2°F
Differential (Heat Pump) ..................... Heat 1.2°F; Cool 1.2°F
Operating Ambient.......................... 32°F to +105°F (0 to +41°C)
Operating Humidity ......................... 90% non-condensing max.
Shipping Temperature Range ................. -40 to +150°F (-40 to +65°C)
Dimensions Thermostat...................... 4.2"H x 6.4"W x 1.7"D
PART NO. 37-6819B
Replaces 37-6819A
1345
www.white-rodgers.com
www.emersonclimate.com
Vue de la page 0
1 2 3 4 5 6 ... 15 16

Résumé du contenu

Page 1 - SPECIFICATIONS

Blue Commercial Thermostat with Automatic Heat/Cool Changeover Option and Damper ControlModel Programming Choices1F95-06807 Day 5/1/1 Day Non-Programm

Page 2 - INSTALLATION

10To prevent compressor and/or property damage, if the outdoor temperature is below 50°F, DO NOT operate the cooling system.CAUTION!Cooling System1.

Page 3 - WIRING DIAGRAMS

11 PROGRAMMINGEnergy Saving Factory Pre-ProgramThe 1F95-0680 thermostats are programmed with the energy saving settings shown in the table below for

Page 4 - WIRING DIAGRAMS

12Automatic Daylight Saving CalculationThe Real Time Clock will adjust automatically for daylight sav-ings time, in the following manner:Increment one

Page 5 - THERMOSTAT QUICK REFERENCE

13Wired Remote Temperature SensingOne remote temperature sensor can be installed indoor or outdoor and connected to the thermostat by a maximum cable

Page 6 - INSTALLER/CONFIGURATION MENU

14Symptom Possible Cause Corrective ActionNo Heat/No Cool/No Fan (common problems)1. Blown fuse or tripped circuit breaker. 2. Furnace power switch to

Page 7

15NOTES

Page 8

HOMEOWNER HELP LINE: 1-800-284-2925White-Rodgers is a business of Emerson Electric Co.The Emerson logo is a trademark and service mark of Emerson El

Page 9 - OPERATING YOUR THERMOSTAT

2Remove Old ThermostatBefore removing wires from old thermostat, mark wires for terminal identification so the proper connections will be made to the n

Page 10 - PROGRAMMING

3 WIRING DIAGRAMSFigure 2 – Single Stage or Multi-Stage System (No Heat Pump) with Single TransformerSingleStage 1(SS1)Multi-Stage 2(MS2)OEnergized

Page 11 - PROGRAMMING

4Single Stage3-wireZone ValveapplicationBlower/CirculatorFan EnergizedOpensValve(4)Constant24 Volt(Com-mon)24 Volt(Hot)CoolSystem6YWCRCCLASS IITRANSFO

Page 12

5Programming and Configuration Items 1 "System On" indicates when heating or cooling stage is energized. "System On +2" indicate

Page 13

6INSTALLER/CONFIGURATION MENU Thermostat must be in Heat, Cool or Auto. Press and hold the Menu button for at least 5 seconds. The display will show i

Page 14 - TROUBLESHOOTING

7 INSTALLER/CONFIGURATION MENU22 21 19 MENU (OFF)Keypad LockoutL, P, Limit Selects one of 3 Keypad Lockout configurationsL - Total Keypad LockoutP -

Page 15

8INSTALLER/CONFIGURATION MENU 5°. Allowing 5 minutes per degree, the thermostat setpoint will change to 70° at 6:35 AM. Cooling allows more time per

Page 16 - The Emerson logo is a

9 INSTALLER/CONFIGURATION MENU or button. 25) Select Compressor Off (CO) Feature Using Outdoor Sensor – This feature is applicable only in heat pu